Push the ‘AUTOMATIC
STOP’ button.
·
The steam booster
valve VA-SI-01 closes.
·
The hot water pump
PU-HW-01 stops.
·
The ejector pump
EC-PU-01 stops.
·
The vacuum breaker
VA-SV-01 opens.
·
The system cools down
for a period of time.
·
The seawater pump
SW-PU-10 stops.
·
The feed water valve
FE-VA-10 closes.
·
The chemical pump
PU-CU-01 stops.
·
The seawater flash
pump PU-SF-01 stops.
·
The seawater flash
drain valve VA-SF-01 opens.
·
The vessels levels
are drained for a period of time.
·
The brine pump
BR-PU-10 stops.
·
The brine valve
VA-BR-06 closes.
·
The distillate pump
PU-DI-01 stops.
·
The distillate valve
VA-DI-01 closes.
For more information see:
Alfa Laval ‘Instruction
manual for desalination units’ – Binder 1/3
- Section 4.4
Normal shut-down.